Evidence
How was each claim checked?
Network data6
Public data cannot show safe hosting capacity: it has no transformer kVA, no consumers per transformer and no 15-minute load.
How it was checked
SME answer, item 2.
(SME label [checked-correct]; not re-checked here)
Limits
Needed from the department: a DTR list with kVA and consumers, 15-minute DTR and feeder metered load, and one real service-number lookup result.
SME answer, item 2
TGSPDCL has a page 'NetMetering Capacity on Distribution Transformer' that takes ONE service number and returns that consumer's DTR. It is a lookup, not a public list of transformers.
How it was checked
Form seen and checked by the SME.
(SME label [checked-correct] for the form; not re-checked here)
Limits
Wording to use: 'lookup exists, no public DTR list found'. Never write 'not published'.
SME answer, item 2
What the TGSPDCL lookup returns for a real service number (the DTR kVA, load, room left).
How it was checked
The SME has never seen the output.
because nobody has seen the output of the lookup
Limits
One real service-number lookup result is needed from the department.
SME answer, item 2
TGNPDCL: no DTR-capacity page was found. Regulation cl 5.2 requires capacity to be published per DTR and feeder.
How it was checked
Negative search by the SME; the regulation clause as read by the SME.
because a negative search is not proof
Limits
Wording: 'lookup exists (TGSPDCL), no public DTR list found'; never 'not published'.
SME answer, item 2
Distribution transformer failure in Telangana is 11 to 13% a year (2015-17) and 15 to 17% in rural circles (Prayas, from discom filings). It is driven by agriculture, not by rooftop solar.
How it was checked
Secondary source as given by the SME.
because only a secondary source (Prayas, from discom filings); SME label [secondary]
Limits
Years 2015-17 only.
SME answer, item 2
Upgrade lead times: nothing on file. Rule 11(8) of the central consumer rules: strengthening for up to 5 kW is paid from the discom's revenue requirement.
How it was checked
SME answer, item 2; no label given for rule 11(8); official text not re-read here.
because no lead-time data is held and the rule text was not re-read here
Limits
Ask the discom for real lead times; they set the 'Act now' and 'Watch' thresholds (PROPOSED - NOT TESTED).
SME answer, item 2
| Table | Source file | Rows | Loaded at (UTC) |
|---|---|---|---|
| annual_yield | results/annual_yield_check.csv | 10 | 2026-11-20T05:58:18+00:00 |
| area_band | results/area_test.csv | 4 | 2026-11-20T05:58:18+00:00 |
| cap_unit_sensitivity | results/hosting_cap_unit_sensitivity.csv | 24 | 2026-11-20T05:58:18+00:00 |
| circle_point | data/irradiance_openmeteo_tgspdcl/README.md | 20 | 2026-11-20T05:58:33+00:00 |
| evidence_item | scripts/evidence_items.json | 56 | 2026-11-20T05:58:31+00:00 |
| feeder_dtr | results/feeder_demo.json | 20 | 2026-11-20T05:58:18+00:00 |
| feeder_meta | results/feeder_demo.json | 3 | 2026-11-20T05:58:18+00:00 |
| forecast_accuracy[monthly] | results/test_monthly.csv | 12 | 2026-11-20T05:58:18+00:00 |
| forecast_accuracy[static] | results/test_static.csv | 12 | 2026-11-20T05:58:18+00:00 |
| forecast_by_point[monthly] | results/test_by_point_monthly.csv | 39 | 2026-11-20T05:58:18+00:00 |
| forecast_by_point[static] | results/test_by_point_static.csv | 39 | 2026-11-20T05:58:18+00:00 |
| forecast_example | results/live_area_example.txt | 24 | 2026-11-20T05:58:18+00:00 |
| forecast_hourly | results/test_predictions_monthly.parquet, results/test_predictions_static.parquet | 231438 | 2026-11-20T05:58:33+00:00 |
| growth_class | TGSPDCL_summary/net_meter_clean_22_months.csv (computed by hosting/growth_classes.py) | 18 | 2026-11-20T05:58:18+00:00 |
| hosting_bootstrap | results/hosting_p5_bootstrap_ci.csv | 9 | 2026-11-20T05:58:18+00:00 |
| hosting_runs[indian] | results/indian_runs.csv | 4200 | 2026-11-20T05:58:18+00:00 |
| hosting_runs[load025] | results/hosting_lv_runs.csv | 540 | 2026-11-20T05:58:18+00:00 |
| hosting_runs[load050] | results/hosting_lv_load050_runs.csv | 540 | 2026-11-20T05:58:18+00:00 |
| hosting_summary[indian] | results/indian_summary.csv | 21 | 2026-11-20T05:58:18+00:00 |
| hosting_summary[load025] | results/hosting_lv_summary.csv | 18 | 2026-11-20T05:58:18+00:00 |
| hosting_summary[load050] | results/hosting_lv_load050_summary.csv | 18 | 2026-11-20T05:58:18+00:00 |
| kusum_cap_sensitivity | results/hosting_kusum_cap_sensitivity.csv | 16 | 2026-11-20T05:58:18+00:00 |
| kusum_grid | results/hosting_kusum.csv | 16 | 2026-11-20T05:58:18+00:00 |
| net_meter_category_month | TGSPDCL_summary/net_meter_clean_22_months.csv | 163 | 2026-11-20T05:58:18+00:00 |
| net_meter_gap | TGSPDCL_summary/net_meter_clean_22_months.csv (derived) | 23 | 2026-11-20T05:58:19+00:00 |
| net_meter_section_month | TGSPDCL_summary/net_meter_clean_22_months.csv | 10099 | 2026-11-20T05:58:18+00:00 |
| net_meter_series_break | TGSPDCL_summary/net_meter_clean_22_months.csv (derived) | 7 | 2026-11-20T05:58:19+00:00 |
| nowcast_backtest | nowcast/results/backtest.csv | 6 | 2026-11-20T05:58:33+00:00 |
| real_dataset | computed from the files above | 8 | 2026-11-20T05:58:31+00:00 |
| real_fact | telangana_reports/mnre_2026_02.pdf; docs/Challenge16_DER_Final.md | 3 | 2026-11-20T05:58:31+00:00 |
| real_not_held | scripts/load_data.py (NOT_HELD) | 5 | 2026-11-20T05:58:31+00:00 |
| saturation | results/indian_months_to_full.csv (safe limit: indian_summary.csv P5 at 1.00 pu) | 21 | 2026-11-20T05:58:18+00:00 |
| weather_coverage | irradiance_openmeteo_tgspdcl/*.csv, prev_day1_tgspdcl/*.csv | 13 | 2026-11-20T05:58:31+00:00 |
| weather_daily | same files, every day, daily totals | 37310 | 2026-11-20T05:58:31+00:00 |
| weather_hourly | same files, last 14 days, hourly | 4368 | 2026-11-20T05:58:31+00:00 |
| weather_point | data/irradiance_openmeteo_tgspdcl/README.md | 13 | 2026-11-20T05:58:33+00:00 |
REAL = measured or published data held in this project. Weather actuals are satellite/reanalysis-based sunlight, not metered solar output. Our model, or a published model reference (PVGIS), run on real inputs. Not measured. Assumed typical values (street lengths, cables, houses, 3 kWp roofs, load per home). The pilot replaces them with the discom's data.
| Dataset | Tag | Period | Rows | Coverage | Last date | Source file | Can show | Cannot show |
|---|---|---|---|---|---|---|---|---|
| TGSPDCL rooftop net-meter records, monthly | REAL | 2025-01 to 2026-10 | 146,665 | 22 monthly files; 20 circles and 473 section offices (circle + section name) in 2026-10; 59,550 services in 2026-10; July 2025 de-duplicated; Aug 2025 has no Gadwal circle (kept missing) | Oct 2026 | data/TGSPDCL/ (22 monthly files, Open Data Telangana) -> data/TGSPDCL_summary/net_meter_clean_22_months.csv | Real billed services, billed kW (load column) and units, by month, circle and section office. | Per-transformer counts, hourly values, what 'units' means (import, export or net). |
| Open-Meteo weather actuals, 13 TGSPDCL points (hourly) | REAL | 2019-01-01 to 2026-11-09 | 895,440 | 13 points, 68,880 hourly rows each; satellite/reanalysis-based archive | 9 Nov 2026 | data/irradiance_openmeteo_tgspdcl/*.csv (Open-Meteo, CC BY 4.0) | Real sunlight (GHI, direct, diffuse), temperature, cloud, wind by hour for the area. | Ground-station measurements, metered solar output, the newest days are provisional (back-filled). |
| Open-Meteo day-before forecasts, 13 TGSPDCL points (hourly) | REAL | 2024-01-19 to 2026-11-09 | 319,891 | 13 points, 24,607 non-empty hourly rows each of 25,056 (the empty hours are before the first real forecast) | 9 Nov 2026 | data/prev_day1_tgspdcl/*.csv (Open-Meteo previous-runs API, CC BY 4.0) | What the weather model forecast one day before, to compare with the actuals above. | Metered solar output; it is a weather forecast, not a solar-power forecast. |
| MNRE state-wise renewable capacity table | REAL | 31.01.2026 | 1 | one Telangana row: rooftop 695.9 MW, solar total 5,065.10 MW | 31.01.2026 | data/telangana_reports/mnre_2026_02.pdf | State-level rooftop and total solar capacity on one date. | A time series (the other dates in the SME note are not held), anything per district, circle or transformer. |
| PM Surya Ghar installations, Telangana (quoted) | REAL | 27 Jul 2026 | 1 | 54,668 installations, 70,144 households (quoted from Lok Sabha Q 1698) | 27 Jul 2026 | docs/Challenge16_DER_Final.md (source file not held) | A state-level count of subsidised rooftop installations. | MW per state, per circle or per transformer. The source file is not held, so the figure cannot be checked yet. |
| PVGIS 1 kWp hourly output (published model reference) | MODEL | not a dated file | n/a | source files not found on this machine | n/a | data/pvgis_1kwp/*.csv | A published model reference for 1 kWp output. | Measured output. |
| Open-Meteo live forecast (called when you ask, LIVE badge) | REAL | not a dated file | n/a | 13 points, next day and the day after; falls back to the stored example when the call fails and says so | n/a | Open-Meteo API (CC BY 4.0) via backend/app/integrations/open_meteo/ | A real weather forecast fed into our shipped model. | The power estimate is modelled: it is not scored against metered output. |
| TGSPDCL guideline and agreement texts, CSTEP feeder report, MNRE table (PDFs) | REAL | not a dated file | n/a | source folder not found on this machine | n/a | data/telangana_reports/*.pdf | The published rules: 50% DTR cap wording, 56 kWp self-certification threshold, the CSTEP feeder method. | The TGERC regulation text and the 2016 gazette are not held; the unit of the 50% cap is not stated in either text. |
- Real transformer data (kVA, consumers, phase, 15-minute DTR or feeder load). Not public; the DTR list has to come from the department. Every network value here is assumed.
- Metered rooftop solar output. Not public and not downloadable (PVGIS stops at 2023; no metered source was found). Forecast accuracy is versus a physics model, not versus measurement.
- Ground-measured sunlight (GHI). No ground station file is held. The Open-Meteo actuals are satellite/reanalysis-based; NIWE or IMD stations would be the check.
- Hourly or 15-minute net-meter / smart-meter data. Only monthly counts, billed kW and units are public. The meaning of the 'units' column (import, export or net) is not documented.
- TGNPDCL (northern discom) net-meter data. No TGNPDCL file was found; the net-meter data covers TGSPDCL only.
- REAL Telangana rooftop solar, MNRE state table: 695.9 MW (as on 31.01.2026; telangana_reports/mnre_2026_02.pdf)Table headed 'State-wise (Location based) installed capacity of Renewable Power as on 31.01.2026', Telangana row. State total, not per transformer.
- REAL Telangana solar power total, MNRE state table: 5,065.1 MW (as on 31.01.2026; telangana_reports/mnre_2026_02.pdf)Same table, 'Solar Power Total' column (ground mounted 4,360.49 + rooftop 695.9 + the third solar column 8.71).
- REAL PM Surya Ghar installations, Telangana: 54,668 installations (as on 27 Jul 2026; docs/Challenge16_DER_Final.md (quotes Lok Sabha Q 1698))Quoted from Lok Sabha Q 1698; the source file is not held, so it cannot be checked yet (the expert review found it correct). 70,144 households in the same answer; no MW per state found.
A traffic light per transformer: reason, room left, early warning. Network values are assumed examples until the discom supplies its own data. Screening only, never approved capacity.
Every claim in this app, how it was checked, and what it cannot tell you. Labels: checked - correct, checked - wrong, cannot be checked yet, because ...
Limit on the street results (E01 to E03 generic sensitivity; E55 Indian headline). P5 is a screening value and can be optimistic. Checks run on the generic 400 V model (not repeated on the Indian model): in 91 of 540 roof-by-roof trials "more roofs is never better" fails, and OpenDSS gives 69.0 vs 73.35 kWp (urban) and 16.35 vs 18.0 kWp (rural), both unbalanced. Treat it as a range, not a guarantee.
P5 as defined here (Passes screening tests). P5 = 5th percentile over 200 random trials (Indian street model, the headline; 30 random trials on the generic 400 V sensitivity) of the largest rooftop solar (3 kWp roofs, panel kWp) that passes the screening tests at the sunniest hour (voltage rise +6%, transformer 100 per cent of rating, cable 100 per cent, unbalance 3%); each trial redraws which homes adopt and (except the balanced and three-phase cases) each home's phase. Each trial value is the largest number of 3 kWp roofs that passes, so it is a multiple of 3 kWp; the 5th percentile interpolates linearly between the sorted values (numpy), so the printed P5 can fall between 3 kWp steps (for example 34.35). P50 is the median of the same trials. Screening value, not a guarantee.